Experiments reveal groundwater temperature impacts energy efficiency in heat pumps, suggesting mapping strategies.
Resource maps for open-loop ground source heat pump (GSHP) systems were developed based on heating and cooling experiments to identify areas with potential for reduced operational costs. Experiments conducted at a public hall, where groundwater temperatures fluctuate seasonally, clarified the relationships between the coefficient of performance (COP) of a heat pump and three key parameters: groundwater temperature, flow rate, and energy consumption. Multiple regression analysis produced equations for estimating the energy consumption of both the heat pump and the water pump. Results indicate that groundwater temperature influences the COP, increasing it by 0.07969 per °C during heating and decreasing it by 0.1721 per °C during cooling. These equations enable the estimation of energy consumption in open-loop systems from groundwater temperature, groundwater depth, and building type. Resource maps developed for the Nobi Plain in central Japan reveal that annual energy consumption is lower in the northwestern region, where groundwater temperatures are generally lower, except in marginal zones for hospitals and offices.
No takes yet. Share an insight, caveat, or question.
Ohtani et al. (2025) studied this question.
Synapse has enriched 5 closely related papers on similar clinical questions. Consider them for comparative context: